| • ioLogik E1242 Specifications | |
| • Inputs and Outputs | |
| Digital Inputs | 4 channels |
| Configurable DIOs (by jumper) | 4 channels |
| Analog Inputs | 4 channels |
| Isolation | 3k VDC 2k Vrms |
| • Digital Input | |
| Sensor Type | Wet Contact (NPN PNP), Dry Contact |
| I/O Mode | DI Event Counter |
| Dry Contact | • On: short to GND • Off: open |
| Wet Contact (DI to COM) | • On: 10 to 30 VDC • Off: 0 to 3 VDC |
| Common Type | 4 points per COM |
| Counter Frequency | 250 Hz |
| Digital Filtering Time Interval | Software Configurable |
| • Digital Output | |
| Type | Sink |
| I/O Mode | DO Pulse Output |
| Pulse Output Frequency | 500 Hz |
| Over-Voltage Protection | 45 VDC |
| Over-Current Protection | 2.6 A (4 channels @ 650 mA) |
| Over-Temperature Shutdown | 175°C (typical), 150°C (min.) |
| Current Rating | 200 mA per channel |
| • Analog Input | |
| Type | Differential input |
| Resolution | 16 bits |
| I/O Mode | Voltage / Current (jumper selectable) |
| Input Range | 0 to 10 VDC, 0 to 20 mA, 4 to 20 mA, 4 to 20 mA (burnout detection) |
| Accuracy | ±0.1% FSR @ 25°C ±0.3% FSR @ -10 and 60°C ±0.5% FSR @ -40 and 75°C |
| Sampling Rate | • All channels: 12 samples/sec • Per channel: 3 samples/sec • Only one channel enabled: 12 samples/sec |
| Input Impedance | 10 mega-ohms (min.) |
| Built-in Resistor for Current Input | 120 ohms |
| • Power Requirements | |
| Input Voltage | 12 to 36 VDC |
| Input Current | 139 mA @ 24 VDC |
| • MTBF (mean time between failures) | |
| Time | 502,210 hrs |
| Standard | Telcordia SR332 |
| • Common Specifications | |
| • LAN | |
| Ethernet | 2 switched 10/100 Mbps RJ45 ports |
| Protection | 1.5 kV magnetic isolation |
| Protocols | Modbus/TCP (Slave), EtherNet/IP*, SNMPv1/v2c, RESTful API, TCP/IP, UDP, DHCP, BOOTP, HTTP |
| • Physical Characteristics | |
| Wiring | I/O cable max. 14 AWG |
| Dimensions | 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in) |
| Weight | Under 200 g (0.44 lb) |
| Mounting | DIN rail wall |
| • Environmental Limits | |
| Operating Temperature | Standard Models: -10 to 60°C (14 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
| Storage Temperature | -40 to 85°C (-40 to 185°F) |
| Ambient Relative Humidity | 5 to 95% (non-condensing) |
| Shock | IEC 60068-2-27 |
| Vibration | IEC 60068-2-6 |
| Altitude | Up to 2000 m |
| Note | Please contact Moxa if you require products guaranteed to function properly at higher altitudes. |
| • Standards and Certifications | |
| Safety | UL 508 |
| EMC | EN 55032, EN 55024, EN 61000-3-2/3-3, EN 61000-6-2/6-4 |
| EMI | CISPR 32, FCC Part 15B Class A |
| EMS | IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 |
| Hazardous Location | Class 1 Division 2, ATEX Zone 2 |
| Green Product | RoHS, CRoHS, WEEE |
| Note | Please check Moxa’s website for the most up-to-date certification status. |
| • Warranty | |
| Warranty Period | 5 years |
| Details | See www.moxa.com/warranty |
| Note | Because of the limited lifetime of power relays, products that use this component are covered by a 2-year warranty. |

MOXA, Remote I/O
ioLogik E1242
Features and Benefits
-
User-definable Modbus/TCP Slave addressing
- Supports EtherNet/IP* adapter mode
- Supports RESTful API for IIoT applications
- 2-port Ethernet switch for daisy-chain topologies
-
Save time and wiring cost with peer-to-peer communications
-
Active communications with MX-AOPC UA Server
-
Supports SNMPv1/v2c
-
Easy mass deployment and configuration with ioSearch utility
-
Friendly configuration via web browser
-
Simplify I/O management with MXIO library on either a Windows Linux platform
-
Class I Division 2, ATEX Zone 2 certification
-
Wide operating temperature range: -40 to 75°C (-40 to 167°F)